How Many Solar Batteries Do I Need? Sizing Worksheet
Last reviewed: . Free reference — no quote or form needed. Methods and limits are stated on this page.
Short answer: count energy, not batteries. Add up the watt-hours your essential loads use per day, divide by inverter efficiency and by the usable fraction of the battery, then divide by one battery's nameplate kWh. In the worked example below, 5 kWh/day of essential AC loads needs about 6.8 kWh of nameplate battery for one day of backup — before any solar recharging during the outage.
Step 1: list essential loads only
Decide what the battery is for. Essentials-only (fridge, lights, internet, phone charging, a laptop) is a very different number from whole-home use with electric heating, cooking or air conditioning. The U.S. Department of Energy's load-analysis method is the right starting point: record each appliance's wattage and its average daily hours of use, accounting for cycling appliances like fridges by their duty share.
Step 2: daily Wh per load = W x hours x duty share
- Fridge: 120 W x 24 h x 40% duty = 1,152 Wh/day
- Lights: 40 W x 6 h = 240 Wh/day
- Router: 10 W x 24 h = 240 Wh/day
- Laptop and phones: roughly 300 Wh/day in this example
- Example extras (fan, TV sessions, small appliances): brings this illustrative household to 5,000 Wh/day of AC energy. Your list will differ — that is the point of the worksheet.
Step 3: convert AC need to nameplate battery size
Battery-side energy per day = AC Wh / efficiency + idle W x 24. With 85% efficiency and 10 W idle: 5,000 / 0.85 + 240 = 6,122 Wh. Nameplate needed = 6,122 / 0.90 usable fraction = about 6,800 Wh (6.8 kWh) per day of no-sun backup. For reference at the same assumptions: 2 kWh/day of essentials needs about 2.9 kWh nameplate per day; 10 kWh/day needs about 13.3 kWh per day. Multiply by the number of backup days you want without recharging, then divide by one battery unit's nameplate kWh and round up to whole units.
Step 4: check power (kW) separately
Total energy says how long; the inverter's continuous kW rating says what can run at the same moment, and motor startup surges need separate headroom. Read kW vs kWh if those two numbers blur together, and test runtime for a single evening with the battery runtime calculator.
Limits of this worksheet
- Solar generation during an outage can extend runtime, but it varies with weather and season; this worksheet deliberately sizes for the no-sun case first.
- Efficiency, usable fraction and idle draw must come from your equipment's documentation, not from this example.
- This is a planning estimate, not a system design. Fixed home battery installation and any mains connection are licensed-professional work; no wiring instructions are given here.
- No prices or product recommendations are made.
Sources
- Planning for Home Renewable Energy Systems (load analysis: wattage x hours of use) — U.S. Department of Energy, Energy Saver. Accessed 2026-11-16.
- Measuring electricity (watts, kilowatts and kilowatt-hours explained) — U.S. Energy Information Administration. Accessed 2026-11-16.
Numbers on this page are worked examples from the stated assumptions, not tests of any product. Always check your own equipment labels and manuals.