Estimate how much heat one room loses, in watts, at temperatures you choose: through its walls, windows and other surfaces, and through air leaving the room. You supply every area and U-value — nothing about your walls is guessed. This is a simplified steady-state worksheet for understanding heat flow, not a heater size or a building-code check.

Calculations stay local in your browser; nothing you enter is sent or stored. Last reviewed 16 November 2026.

1 · Temperatures
2 · Surfaces that lose heat (net areas)

Enter each surface's net area: the opaque wall area must exclude the window area in it, and windows are entered as their own surface. Nothing is subtracted automatically. Add floor or ceiling rows only where the other side is meaningfully colder (for example an unheated space); surfaces against rooms at the same temperature can be left out or entered with area 0. U-values are always entered in W/m²K, whatever area unit you pick — see the note under the form.

Surface 1

Surface 2

3 · Air leaving the room

Worked example (the pre-filled numbers)

Example assumptions only — the areas, U-values and air-change rate below are illustrative entries, not facts or defaults for any material or home. Inside 20 °C, outside 0 °C, so ΔT = 20 K. Walls: 100 m² × U 0.3 × 20 = 600 W. Windows: 10 m² × U 1.4 × 20 = 280 W. Through surfaces: 880 W. Air: 0.33 × 0.5 ACH × 200 m³ × 20 = 660 W. Total: about 1,540 W.

Method

Through each surface, heat flow in watts is U × net area × temperature difference, summed over all surfaces. Through air exchange it is approximately 0.33 × ACH × room volume in m³ × temperature difference. The 0.33 is a rounded constant, not an exact value: air's volumetric heat capacity is about 1,200 J/m³K, and 1,200 ÷ 3,600 s/h ≈ 0.333…, which this worksheet further rounds to 0.33. Areas in ft² are converted to m² and volumes in ft³ to m³ before use (1 ft = 0.3048 m exactly). Fahrenheit temperatures are converted to Celsius first, so a 36 °F difference correctly becomes a 20 K difference. If inside is not warmer than outside, the worksheet reports no heating heat loss rather than a negative number.

Your U-values must be in W/m²K for this page. If your figures are given as R-values or in imperial units, use the insulation U-value and R-value converter. This page offers no material menu, because a U-value belongs to a specific construction, not to a material name.

Limitations

Real rooms are not steady-state boxes. This worksheet ignores solar gains through glazing, heat from people and appliances, thermal bridging at junctions, wind-driven changes in leakage, moisture, thermal mass, and heat flow to neighbouring rooms at different temperatures; it also treats your ACH as constant. Results are only as good as the areas, U-values and ACH you enter, and are stated to the nearest watt for readability, not because the model is that precise. The total describes heat flow at the temperatures you chose: it does not recommend a heater or heat-pump size, and it is not a building-code or energy-rating assessment. For sizing or compliance, a qualified heating designer using the relevant national method is the right route.

Sources

Framework of fabric heat loss via element areas and U-values, as used in official dwelling energy methods: UK government, Standard Assessment Procedure (SAP) overview and Approved Document L (England; cited for the U×A framework only — no requirement values are used here, and other countries use their own methods). Unit conversions and the exact foot: NIST Guide to the SI, Appendix B.8. SI temperature and watt definitions: BIPM. The 0.33 air coefficient is a rounded engineering approximation (≈0.333… from about 1,200 ÷ 3,600, rounded to 0.33), not an exact constant; treat it as approximate.